Home > News Center
Sep.02.2026
Author: Leikeshi
Click: 0
We supply grounding materials, but we have also seen many projects fail inspection for reasons that had little to do with the materials themselves. In many cases, the real problems come from installation details that are easy to overlook.
Here are some of the most common issues encountered before and during grounding grid inspection and acceptance—lessons worth noting for both contractors and project owners.
Connection points are one of the first things inspectors focus on when excavation checks are required.
For conventional welded connections, common defects include incomplete welding, undercutting, and weld slag that has not been properly removed.
Exothermic welding has its own potential problems. If the graphite mold is not properly dried, gas pores may form in the joint. If the conductor surface is not cleaned and polished before welding, proper bonding may not be achieved.
One particularly common mistake is using damp exothermic welding powder. Moisture can seriously affect the reaction and joint quality. If the welding powder has absorbed moisture, it should be replaced rather than reused.
During inspection, connection points may be visually examined and mechanically checked. Defective or poorly formed joints are likely to be identified immediately.
Good connection quality is essential because a grounding grid is only as reliable as its weakest connection.
After the grounding conductors are installed, many contractors underestimate the importance of backfilling.
Simply putting excavated soil and stones back into the trench can leave voids around the grounding conductor. Large stones may prevent close contact between the conductor and surrounding soil, increasing contact resistance and making it difficult to achieve the required grounding resistance.
The recommended practice is to use suitable fine soil for backfilling and compact it in layers. Where grounding enhancement compounds are specified, they should be installed according to the manufacturer's recommended application procedure.
Proper backfilling can make a significant difference to the final grounding performance.
Ground resistance testing can produce misleading results if the test electrode arrangement is not properly designed.
The current electrode and potential electrode must be installed at adequate distances from the grounding grid. If the test area is too small or the electrodes are placed incorrectly, the measured resistance may not accurately represent the actual grounding performance.
This can lead to a common situation: the contractor's initial test passes, while an independent inspection later produces a significantly different result.
Test distances should therefore be determined according to the size and geometry of the grounding grid and the applicable testing method. Where site conditions are restricted, measurements should be repeated in different directions or using an appropriate alternative method rather than relying on a single questionable reading.
Small installation details can also become major inspection issues.
Disconnecting links, grounding terminals, test points and identification markings are normally shown on the design drawings, but they are sometimes omitted during construction because they are considered unnecessary or inconvenient.
During acceptance, inspectors may check the completed installation against the drawings item by item. Missing components can result in corrective work and delays.
Grounding identification is also important. Appropriate grounding labels, warning signs and color markings should be provided according to the applicable project standards and electrical codes.
These details may seem minor, but they are an important part of a complete and maintainable grounding system.
Documentation may not affect the physical grounding grid directly, but it can have a major impact on project acceptance.
Important records may include:
Material certificates and inspection records
Grounding conductor specifications
Galvanizing or coating thickness test reports
Copper layer thickness and quality reports for copper-clad steel
Welding inspection records
Exothermic welding records
Concealed-work inspection records
Ground resistance test results
As-built drawings and installation records
For example, if the required coating thickness or copper layer test reports are missing, the inspector may require additional on-site testing.
Complete documentation helps demonstrate that the installed grounding system complies with the approved design and specified material requirements.
One practice that is becoming increasingly important is photographic documentation.
Before the grounding grid is covered, take clear photos showing:
Actual burial depth
Conductor dimensions and specifications
Connection and welding points
Grounding terminals and test points
Installation locations corresponding to the drawings
It is recommended to include a measuring tape in burial-depth photographs so the actual depth can be verified visually.
Each connection point should also be clearly numbered and matched with the corresponding location on the drawings. This makes future inspection and maintenance much easier.
These records cost almost nothing to create, but they can become extremely valuable if a dispute occurs or if the grounding system needs to be evaluated years later.
More importantly, construction records should be maintained throughout the project rather than being recreated immediately before inspection. Experienced inspectors can often identify incomplete or reconstructed documentation.
The most effective way to avoid grounding grid acceptance problems is simple:
Do not wait until inspection to start thinking about inspection requirements.
Provide the acceptance criteria and project specifications to the installation team before construction begins. Contractors should build the grounding system according to the inspection requirements from the very beginning.
A grounding grid is a concealed underground system. Once it has been backfilled, many installation problems can no longer be seen without excavation.
If a defect is discovered after the system has been covered, the cost of correction can be many times higher than the cost of doing the work correctly in the first place.
A reliable grounding system is not determined by the grounding material alone.
Material quality, connection technology, backfilling, testing, documentation and construction management all contribute to the final performance of the system.
For grounding grid projects, build it correctly, test it properly, document it completely, and verify every critical detail before backfilling.
A few extra minutes spent on quality control today can prevent years of maintenance problems tomorrow.
Previous: The annual China Lightning Protection technology and products exhibition successfully concluded
Next: Qingdao Leikeshi stone quality system training meeting and safety production meeting